For networks with insignificant non-linear loads: (NLL ≤ 10 %).
Standard voltage disturbances.
Standard operating temperature up to 55 °C.
Normal switching frequency up to 5000 /year.
Maximum current (including harmonics) is 1.5 x IN.
Optimized design for low weight, compactness and reliability to ensure easy installation and
upto 20% space savings in cubicles.
01- New CLAMPTITE terminals that allows maintained tightness.
02- Non accessaile in-built discharge resistors to ensure safety.
03- 1 point for mounting and earthing.
04- Simultaneous and safe disconnection of all the phases at end of life in EasyCan.
05- Stacked design and resin filled technology for better cooling.
01- Self-healing.
02- Pressure-sensitive disconnector on all three phases.
03- Discharge resistors fitted – non removable.
04- Finger-proof CLAMPTITE terminals to reduce risk of accidental contact and to ensure firm
termination (10 to 30.3 kvar in three phase and 8.3 – 15.1 kvar in single phase ).
Constructed internally with single-phase capacitor elements assembled in an
optimized design. Each capacitor element is manufactured with metallized
polypropylene film.
The active capacitor elements are encapsulated in a specially formulated
biodegradable, non-PCB, polyurethane soft resin which ensures thermal stability
and heat removal from inside the capacitor.
The unique finger-proof CLAMPTITE termination is fully integrated with discharge
resistors and allows suitable access to tightening and allows cable termination
without any loose connections.
For lower ratings, double fast-on terminals with wires are provided.
01- Easy installation
02- Easy for reliablity and safe usage.
03- Easy for quality assurance.
04- Easy choice for building your solutions with other Schneider Electric components.
05- Easy choice for savings.
Standards IEC : 60831-1/2
Voltage range :230V to 525V in Three Phase & 220-440V in Single Phase
Frequency :50 / 60Hz
Power range :1 to 30.3 kvar
Losses (dielectric): < 0.2W/ kvar
Losses (total) :< 0.5W/ kvar
Capacitance tolerance :-5 %, +10 %
Voltage test Between terminals :2.15 x UN (AC), 10s Between terminal & container
Impulse voltage: 8 kV
Discharge resistor Fitted, standard discharge time :60s
Ambient temperature: -25 / 55 °C (Class D)
Humidity: 95 %
Altitude: 2,000 m above sea level
Overvoltage :1.1xUN 8 h in every 24 h
Overcurrent: Up to 1.5xIN
Peak inrush current: 200x IN
Switching operations (max.): Up to 5,000 switching operations per year
Mean Life expectancy :Up to 100,000 hrs
Harmonic content withstand :NLL ≤ 10 %